AS 1851 counting
The app keeps the tally so nobody works it out from last visit's paperwork.
of the smoke detectors on each loop, every year. All of them within two years.
of the heat detectors on each loop, every year. All of them within five years.
manual call points, flame detectors, beam detectors and any detector that triggers a suppression system, every year.
These are the AS 1851-2012 figures as used in the Magnifire app, counted on each circuit (each loop on an addressable panel).
AS 1851 sample method. The figures above, counted loop by loop.
Every device, every year. For sites where the owner or the contract asks for all devices to be tested annually.
The method is set site by site, in the app or the portal.
The number on the technician's screen is how many more devices have to pass for the site to meet the year's target under the method chosen. Failed devices waiting on a repair are shown separately.
The tester keeps the count. It doesn't replace your own reading of the standard or what your contract requires.
In the demo, fail a device and see the extra 10 appear. Fail a second on the same loop and the whole loop becomes due.